What Size Window Air Conditioner Do I Need?
Window air conditioners are sold in fixed sizes, not made to order — so the job is matching your room to the nearest stocked size above its load, then checking the unit actually fits the window. The chart below does the first part; the tape measure does the second.
Checked and reviewed by Zia ur Rehman, site owner · Last reviewed: November 2026 · The formula is shown on this page and the sources behind the numbers are listed at the foot of the page.
The short answer: work out the BTU, then buy the next size up
A room needs about 20 BTU per square foot of cooling — the starting point of the BTU Calculator and the US Department of Energy's room-air-conditioner guidance. But window units are not made to order: they come in fixed steps — 5,000, 6,000, 8,000, 10,000, 12,000 and 14,000 BTU — so the size you buy is the first stocked step at or above your room's load. A room that needs 7,000 BTU buys an 8,000 BTU unit; a room that needs 9,625 buys a 10,000. Buying the step below the load leaves a unit that runs all day and never quite catches up, while buying two steps above it wastes money and cools the room in short, clammy bursts. Every number on this page matches the calculator — the worked examples below use its exact adjustments.
The largest common window unit is 12,000 BTU, which is also 1 ton of cooling. A 14,000 BTU unit is the top of the usual window range, and above that the choice changes: 18,000 and 24,000 BTU window units exist, but they are scarce, heavy, and usually need a 230-volt outlet — for most rooms over about 700 sq ft, two smaller units or a mini-split is the better buy. Our guide to how many BTUs are in a ton explains where window units end and central-system sizing begins, and our guide to what size air conditioner you need covers the whole-home sizing that central and mini-split systems use.
Window AC size by room
The table uses the baseline of 20 BTU per square foot, for a moderate climate with average insulation and standard 8 ft ceilings, and the "buy" column is the next stocked size at or above the load. If your room has any of the adjustments in the next section — hot climate, strong sun, poor insulation, high ceilings, extra people or a kitchen — work the adjusted load first and read the table from that number instead.
| Room size | Cooling load (20 BTU/sq ft) | Buy this window unit |
|---|---|---|
| 100 sq ft | 2,000 BTU | 5,000 BTU (smallest made) |
| 150 sq ft | 3,000 BTU | 5,000 BTU |
| 200 sq ft | 4,000 BTU | 5,000 BTU |
| 250 sq ft | 5,000 BTU | 5,000 BTU |
| 300 sq ft | 6,000 BTU | 6,000 BTU |
| 350 sq ft | 7,000 BTU | 8,000 BTU |
| 400 sq ft | 8,000 BTU | 8,000 BTU |
| 450 sq ft | 9,000 BTU | 10,000 BTU |
| 500 sq ft | 10,000 BTU | 10,000 BTU |
| 550 sq ft | 11,000 BTU | 12,000 BTU |
| 600 sq ft | 12,000 BTU | 12,000 BTU (1 ton) |
| 700 sq ft | 14,000 BTU | 14,000 BTU (top of the window range) |
Notice how the smallest rooms all land on the same buy: anything up to 250 sq ft needs a 5,000 BTU unit simply because nothing smaller is sold. That is fine — a slightly oversized unit in a small room is a minor inefficiency, not a problem, and it is the only option on the shelf. The table also shows why the 12,000 BTU size is the workhorse of the range: it covers the 550–600 sq ft rooms that a single window unit can still handle on its own.
The adjustments that move the answer
The calculator applies these in order, and the worked examples below show the arithmetic. Start from 20 BTU per square foot, then:
Climate: multiply by 0.9 in a mild climate, 1.0 in a moderate one, and 1.25 in a hot one. Insulation: multiply by 0.9 for good insulation, 1.0 for average, and 1.2 for poor insulation. Sun: multiply by 1.1 for a sunny room, especially a west-facing one. Ceiling height: add 5% for every foot above 8 ft — a 9 ft ceiling is ×1.05, a 10 ft ceiling ×1.10, a 12 ft ceiling ×1.20. People: add 600 BTU for each person over two in the room. Kitchen: add 4,000 BTU for cooking heat. Our guide to BTUs per square foot works through each adjustment in full, including the heating rates that do not apply to a window unit at all.
Worked examples
A 100 sq ft home office, one person. 100 × 20 = 2,000 BTU. The smallest stocked unit is 5,000 BTU, so buy a 5,000 BTU unit. It is more than double the load on paper, and that is normal at this size — the room will cool fast, and the unit's thermostat will cycle it off. Do not hunt for a smaller unit; there is not one to find.
A 250 sq ft master bedroom with 9 ft ceilings, two people. 250 × 20 = 5,000 BTU at the baseline, and the 9 ft ceiling adds 5%: 5,000 × 1.05 = 5,250 BTU. The next stocked size above 5,250 is 6,000 BTU, so buy the 6,000 unit — the 5,000 would be 250 BTU short, and a bedroom that never quite cools at night is the one you notice.
A 350 sq ft living room, hot climate, sunny west-facing windows. 350 × 20 = 7,000 BTU at the baseline. Hot climate (×1.25) and sun (×1.1) together: 7,000 × 1.25 × 1.1 = 9,625 BTU, so buy a 10,000 BTU unit. The bare table says 8,000 for a 350 sq ft room — and that is exactly how a living room gets undersized: the chart row is the starting point, and the sun and climate are what the chart cannot see.
A 450 sq ft studio apartment with a kitchenette. 450 × 20 = 9,000 BTU, plus 4,000 BTU for the cooking heat = 13,000 BTU, so buy a 14,000 BTU unit. A studio is the classic kitchen case: the cooking heat is a quarter of the total load, and leaving it out buys a unit that copes fine until dinner, then loses the room for the rest of the evening.
A 300 sq ft room shared by three people. 300 × 20 = 6,000 BTU, plus 600 BTU for the third person = 6,600 BTU, so buy an 8,000 BTU unit — the 6,000 is 600 BTU short. People are a small adjustment, but they are the one that tips a room from one stocked size to the next.
A 500 sq ft converted garage, poor insulation, 10 ft ceiling. 500 × 20 = 10,000 BTU at the baseline. Poor insulation (×1.2) and the 10 ft ceiling (+10%) together: 10,000 × 1.2 × 1.10 = 13,200 BTU, so buy a 14,000 BTU unit. A converted garage is the hardest room a window unit ever has to cool — thin walls, a high ceiling and often no insulation in the roof — so if the load works out above 14,000 BTU, stop and think about a mini-split instead of forcing a window unit to do a job it was not built for.
Will it fit the window?
Size the BTU first, then check the fit — a perfect 10,000 BTU unit is useless in a window it cannot sit in. Measure the opening, not the frame: the width between the side jambs and the height the lower sash can open. Most 5,000–12,000 BTU units fit windows 23–36 inches wide and need at least 13–15 inches of open height, but the exact range is printed on the box — check it before you buy, because a unit that is an inch too wide does not fit at any price. Window units are made for double-hung windows (the kind that slide up and down); casement windows that crank open and horizontal sliders need a special kit or a different unit altogether.
Two fitting details people get wrong: first, the support bracket — units above about 10,000 BTU are heavy, and most manufacturers want a bracket screwed to the outside wall or sill rather than the window frame alone carrying the weight. Second, the tilt — the unit must slope very slightly outward so condensation drains outside, not onto your floor. The accordion side panels close the gaps beside the unit; seal any remaining gaps with foam, or the hot air you just paid to remove comes straight back in around the edges.
Voltage and efficiency — check before you buy
Most window units up to 12,000–14,000 BTU run on a standard 115-volt household outlet, but larger units often need a 230-volt outlet — the kind a dryer or a large appliance uses. Check the plug and the voltage on the box against the outlet near the window before buying: a 230-volt unit will not run on a 115-volt outlet, and adding a new circuit costs more than the difference between unit sizes. If the room has only one outlet and it is already shared with other equipment, check the circuit too — an 8,000 BTU unit draws roughly 700 watts, and a 15-amp circuit has only so much to give.
Efficiency is measured as EER — BTU of cooling per watt of electricity. An 8,000 BTU unit with an EER of 12 uses about 8,000 ÷ 12 = 667 watts; the same capacity at an EER of 10 uses 800 watts for the same cooling, and the difference shows up on every summer electricity bill. Look for a CEER (the current combined rating) of 12 or higher, and prefer an Energy Star unit — the rating is printed on the yellow EnergyGuide label, so two units of the same BTU can be compared in the store in seconds.
Costs — rough ranges only
US retail prices, roughly: a 5,000 BTU unit $150–$300, an 8,000 BTU unit $250–$400, a 10,000 BTU unit $300–$450, a 12,000 BTU unit $350–$550 and a 14,000 BTU unit $400–$600 — before the bracket, the foam and any installation help. A higher-EER unit costs more up front and less every month it runs, so compare the price difference against a summer of electricity before choosing the cheapest box. Installation is usually a DIY job for a 5,000–8,000 BTU unit and a two-person job above 10,000 BTU, because of the weight and the bracket.
Common mistakes
- Buying the stocked size below the load. A 9,625 BTU load buys a 10,000 BTU unit, not an 8,000. Round up to the next size — never down.
- Sizing from square footage alone. Sun, climate, ceiling height, people and a kitchen can move a room two stocked sizes. Work the adjustments, then read the chart.
- Measuring the window frame instead of the opening. The unit has to fit between the jambs with the sash raised. Measure the opening, then check the box's fit range.
- Forgetting the voltage. A 230-volt unit will not run on a standard outlet. Check the plug before the purchase, not after.
- Oversizing badly. A 14,000 BTU unit in a 150 sq ft room cools the air in minutes, then shuts off before it has pulled the humidity out — cold and clammy. One step up is right; three steps up is a mistake.
- Installing it level or tilted inward. The unit must slope slightly outward so condensation drains outside. Level means puddles on the floor.
Frequently Asked Questions
What size window air conditioner do I need for a 12x12 room?
A 12×12 ft room is 144 sq ft, so 144 × 20 = 2,880 BTU at the baseline — buy a 5,000 BTU unit, the smallest stocked size. If the room is hot, sunny or has a high ceiling, the load rises to around 4,000 BTU, which is still a 5,000 BTU unit.
What size window AC for a 400 sq ft room?
8,000 BTU at the baseline — 400 × 20 = 8,000, which lands exactly on a stocked size. With a hot climate, strong sun or poor insulation the load rises toward 10,000 BTU, so buy the 10,000 BTU unit if any of those apply.
Can I put a 12,000 BTU window AC in a small room?
You can, but you should not go far above the load: a 12,000 BTU unit in a 150 sq ft room cools the air fast, then shuts off before it removes the humidity, leaving the room cold and clammy. One stocked size above the load is right; several sizes above is a mistake.
What size window do I need for a window air conditioner?
Most 5,000–12,000 BTU units fit double-hung windows 23–36 inches wide with at least 13–15 inches of open height — but check the exact fit range printed on the box, because it varies by model. Casement and sliding windows need a special kit.
Does a window AC need a 220 volt outlet?
Usually not up to 12,000–14,000 BTU, which run on a standard 115-volt outlet. Larger window units often need a 230-volt outlet, so check the plug and voltage on the box against the outlet near the window before buying.
Sources and Method
The constants and rules of thumb on this page come from the published references below. Where a figure is a range, the calculator uses the mid-range value and the text says so.
- ACCA Manual J — the professional residential heating and cooling load calculation this quick estimate does not replace.
- US Department of Energy, Energy Saver — room air conditioner sizing guidance (about 20 BTU per sq ft as a starting point, 600 BTU per extra occupant, 4,000 BTU for a kitchen).